Abstract

Since in their tenders for subway fire alarm system contracts some fire detector manufacturers recently claimed that the RF electromagnetic field strength to which their products can resist is much higher than the requirements of the relevant national technical standards on fire, we have conducted tests on the RF electromagnetic field strength around the fire detectors installed on the platform of a number of selected subway stations in Guangzhou, and the performances of the electromagnetic radiation analyzer used for the tests are strictly in compliance with the specified use conditions for fire detectors installed on the platform in subway stations. The test results show that the RF electromagnetic field strength applied in the RF radiated immunity test as specified in relevant national standards conforms to the current application conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.