Abstract

A sub-synchronous oscillation (SSO) suppression strategy of attaching virtual resistance controllers to the rotor-side converter (RSC) of the doubly-fed induction generator (DFIG) is proposed in this study to suppress sub-synchronous oscillation (SSO) caused by series compensation and grid connection of DFIG. A DFIG-based frequency domain impedance model considering RSC control under small signal perturbations is developed in a three-phase stationary coordinate system. Subsequently, the factors and mechanisms of SSO in the system with different phase sequences are analyzed in combination with the equivalent RLC resonant circuit of a DFIG-based series-compensated grid-connected system (SCGCS). SSO occurs when RSC and rotor winding generate a large equivalent negative resistance at the SSO frequency, resulting in a negative total system resistance. Additionally, the influences of series compensation degree (SCD) of line and inner loop parameters (ILPs) of RSC related to the total impedance of the system on the SSO characteristics are analyzed to optimize the parameters and improve the system stability. Based on the causes of SSO, virtual resistance controllers are attached to RSC to provide positive resistance to the system and to offset the equivalent negative resistance of RSC and rotor winding at the SSO frequency, thereby avoiding SSO of the system. Finally, time-domain simulations using power system computer aided design/electromagnetic transients including dc (PSCAD/EMTDC) show that the SSO of the system is effectively suppressed.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call