Abstract
As the 750kV substation has the characteristics like timing inconsistency, dual protection configuration and uncertain diagnosis result, a fault diagnosis method of substation with redundant protection configuration based on time sequence fuzzy Petri nets is proposed. In this method, redundant knowledge about fault component is represented by using two sets of protective information. On that basis, component redundant diagnosis-model based on time sequence fuzzy Petri net is constructed, which can be decomposed into main and redundant subnet-model, in which initial-information credibility is determined by using information-entropy, the time sequence constraint is checked and initial-information credibility is corrected by using the relationship between acted protection and breaker. Compared with fuzzy Petri net diagnosis method taking no account of time sequence factor, the proposed method can not only identify the malfunction information, but also obtain a certain result. DOI: http://dx.doi.org/10.11591/telkomnika.v11i9.2528
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TELKOMNIKA Indonesian Journal of Electrical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.