Abstract

The electrical performance of insulators under comprehensive conditions including low air pressure, pollution and icing, is an important basis for the selection of external insulation. However, the problem of cold wet deposition has not attracted extensive and considerable interest in research. Based on flashover tests of suspension insulators in field test station, the AC flashover performance of insulators was studied. The results show that the duration of existence of the arc throughout the composite insulator surface in case of condensation was significantly lower than that in case of freezing fog flashover because of a change of the sheds surface roughness, which leads the arc melt the frozen fog droplets on the sheds surface and extends its flashover time. Compared with the flashover characteristics of the hydrophilic insulators in frost fog, the composite insulators exhibited clear arc extinguishing and arc starting phenomena. Moreover, the wind velocity has affected the flashover performance of suspension insulators in cold fog. Studying flashover characteristics of suspension insulators can contribute to the design of the external insulation of transmission lines and substations under natural cold fog and wet deposition regions.

Highlights

  • The electrical characteristics of insulators in transmission lines play a decisive role in the safety of power systems [1]

  • The pwer line corridor inevitably passes through areas with cold and wet deposition, where the ice and snow significantly reduce the electrical strength of the insulator [3], [4]

  • In light of the above, this paper examines cold fog flashover in suspension insulators in an environment featuring cold and wet deposition

Read more

Summary

Introduction

The electrical characteristics of insulators in transmission lines play a decisive role in the safety of power systems [1]. A field test was carried out in the Field Scientific Observation and Research Station of the Ministry of Energy Equipment Safety in Xuefeng Mountain to study the characteristics of strings of a suspension insulator in case of ac cold fog flashover.

Results
Conclusion

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.