A study was performed to determine the switching surge voltages a prototype 1200 kV CGIT cable may be exposed to under service conditions. The results of this study were used to establish the system's basic switching impulse insulation level requirements. An investigation was made of a suitable CGIT model to be employed for use on the Westinghouse transient network analyzer. The model chosen was applicable for the cable when its sheaths are solidly grounded. This model was employed for each of the four cable lengths investigated. Cable lengths of 600 ft, 2 miles, 10 miles and 50 miles were investigated in four general system configurations, in all 47 systems were studied.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.