The purpose of the current study is to utilise a novel technology that is expected to bring reductions in electrical and heat energy consumption and cut CO2 emissions in the shopping centre public utility building in Mielec. The building is equipped with systems for obtaining heat and cold from groundwater and features the energy consumption level of a passive building with the lowest primary energy ratio (PER) in Poland. This state-of-the-art, innovative, energy-efficient and environment-friendly FCH system with BMS control was subjected to numerous tests and analyses, the details of which will be presented further in this paper. The design assumptions were confirmed and all work parameters were recorded for the system under extreme conditions, including the determination of final energy (FE) and primary energy (PE).