Abstract
The mathematical model VSC-HVDC system in dq reference frame is derived.For the VSC-HVDC system of transmitting power to passive network ,a constant DC voltage is used in the rectifier-side;a constant AC voltage controller is used in the inverter-side.Digital simulation models are set up by MATLAB/Simulink. Simulation results verify that VSC-HVDC has a independent control of active and passive power,and demonstrates superiority of transmitting active and passive power simultaneously when connecting to passive network.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.