Abstract

Four hot-gas bypass defrosting configurations for CO2-NH3 cascade blast freezer for application in fish processing firm are numerically investigated. Due to the high moisture content of fish, defrosting is necessary after every 4 to 5 h of batch operation. A thermodynamic model for the cascade system and defrosting was developed to study various defrosting configurations formulated by rearranging the existing compressor to operate as a defrosting compressor and with the addition of an external defrosting compressor. From the simulation findings, it can be summarized that the conventional hot-gas bypass defrosting without defrost compressor is suitable for a high-capacity cascade refrigeration system with more than three evaporators. For low cooling capacity refrigeration systems, a defrosting compressor is necessary to elevate the temperature above the cascade condensing temperature. A dedicated defrosting compressor with a power consumption of 3.1 kW and a modified refrigeration/defrosting compressor with a power consumption of 6.8 kW can deliver 33.3 kW of heating at a temperature of +10 °C (45 bar). Incorporating a desuperheater between the main and defrosting compressors reduces compressor temperature and maintains the lubricating oil stability, without change in defrosting energy consumption and less exergy loss. The defrosting efficiency is obtained in the range of 39.7–42% which is in agreement with published literature.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.