Abstract

Considering the negative resistance effect of power electronic equipment, unstable resonance problems may occur between wind farms and converter stations. This paper focuses on the resonance stability problem of a wind power base coupling with a multi-level converter−high-voltage direct-current transmission (MMC–HVDC) system. Firstly, the s-domain impedance models of the doubly-fed induction wind generator, the permanent magnet synchronous wind generator, and the modular MMC are built, through the theoretical derivation and simulation test. Secondly, based on the s-domain nodal admittance matrix method, the resonance structure of the wind power base coupling with an MMC–HVDC system is analysed, including the resonance mode frequencies, the resonance mode damping factors, the nodal participation factors, and the nodal voltage mode shapes. Thirdly, the main factors influencing the resonance structure are studied, including the topology of the wind power base, the capacity of the wind turbines, and the operation mode of the MMC station. Finally, a brief conclusion ends the paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.