Abstract

According to the lightning monitoring data recorded by lightning location system of Guangdong power grid in the past 10 years (from 2003 to 2012), we gain the lightning parameters of Shenzhen power grid and fit the lightning current amplitude distribution curve. The research results show that the fitting expression format of the lightning current amplitude distribution gotten from lightning location system adopted by IEEE is better than that adopted by national power industry regulations. And the lightning current in Shenzhen area ranging from 20kA to 40kA shows obvious packing effect. It’s recommended to take anti-accident measures in the weak sections of mountain areas to improve the shielding failure lightning protection performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.