Abstract
Aiming at the three UHVDC controller model in the electromechanical simulation software BPA which widely used in China, the structural features were analyzed. By the time-domain simulation, the influence of different simulation models and the key controller parameters on the recovery characteristics of the receiving end power system were studied. Simulation results show that the commutation failure simulated method impacts the recovery characteristic significantly for weak power grids, increasing the voltage measurement time constant of constant dc power control module and enhancing the start voltage threshold of voltage dependent current order limit (VDCOL) can decrease the reactive power consumption of inverter during the disturbance, and can help to improve the recovery characteristic of receiving end power grid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of International Council on Electrical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.