Abstract

This study analyzes the recovery voltage changes when a low-voltage circuit breaker opens with load and short-circuit faults and explains the reignition types under different recovery voltages. Reignition probability models of a single-pole contact and three-pole contact under different reignition types are established. The variation law of the contact erosion amount with the arc starting phase angle is analyzed. The distribution characteristics of the electrical life under three reignition types are obtained by simulating the low-voltage circuit breaker electrical life with a random arc starting phase angle. The results show that the electrical life of contacts obviously decreases after reignition, and that the electrical life changes differently with different reignition types. Specifically, the electrical life of a single-pole contact and three-pole contact is reduced by different degrees for the same reignition type. Hence, the influence of reignition on the electrical life distribution characteristics of a low-voltage circuit breaker cannot be ignored.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.