Abstract

The fusion of primary and secondary functions refers to integrating the function of primary equipment and secondary equipment together. If doing so, the working condition of the equipment for primary and secondary fusion becomes more and more complex and bad, especially the transformer working in the smaller workspace after fusing. Therefore, this paper focuses on the transformer used in primary and secondary fusion pole-mounted Switchgear and establishes the temperature field and electric field simulation model of the primary and secondary fusion pole-mounted switchgear transformer, respectively, and the temperature rise and the environment electric field interference influencing the error of transformer are analyzed as well. When the working environment temperature ranges from -40 to 70°C, the maximum error of low-power current transformers and resistive voltage transformers is 0.1246% and 0.0371%, respectively. The electric field is one of the main factors influencing resistive voltage transformers, which makes ratio errors and angle errors -0.256% and -22.5392’, respectively. The research reveals that under conditions, the error is mainly dependent on temperature rise and electric field. These two factors have a great influence on the error, while the transformers still have enough reliability.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call