Abstract

The composite material crossarm has excellent insulation, water repellency, light weight and high strength, which can effectively improve the safety level of the power line. Research results showed that the dry flash lightning voltage and wet flash frequency voltage of the composite crossarms were increased by 50% and 39% respectively, compared to the angle steel crossarms fixed with the same size insulator and the same air gap; corresponding wet frequency withstand voltage and filthy resistance voltage were increased by 117% and 30%, respectively; and the wet and filthy flashover all occurred on the surface of the composite material crossarms.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.