Abstract

Hydrogen safety is a critical component of modern industrial safety production. In this study, a set of hydrogen explosion suppression equipment is designed independently. The suppression effects of the equipment on hydrogen explosions are studied at normal room temperature and pressure. The experimental results show that the actuation time of the equipment and the spraying mode of the suppressant are the main factors leading to the failure of the hydrogen explosion suppression equipment. The flame, with a hydrogen equivalence ratio of 0.7 and 1.0, spreads out of control when the suppressant touches the flame front. At this time, the addition of the suppressant enhances flame propagation and increases pressure. In addition, because the suppressant does not fully cover the developing flame, the hydrogen flame with the equivalence ratio of 0.5 eventually breaks through the suppressant cloud, and the explosion happens. However, when the initial flame is completely covered by the suppressant, the hydrogen explosion is suppressed by hydrogen explosion suppression equipment. This research provides a solid and reliable foundation for hydrogen explosion suppression equipment in industrial safety and production protection.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.