Abstract

With the growing public awareness of environmental protection, the dc ground-level total electric field (TEF) is attracting increasing attention. Especially in high-altitude areas, it has become a key technical factor in deciding conductor types and the height of the transmission line. To determine the altitude effect and correction of the ground-level TEF for HVdc transmission lines, four short bipolar test lines with bundle conductors with the same parameters were built in China at altitudes of 50, 1700, 3400, and 4300 m. Using the test facilities, the dc ground-level TEF was measured over a long period of time, from Jan. 2010 to Nov. 2015. Through a statistical analysis of a large amount of data, the ground-level TEF characteristics of short bipolar test lines at different altitudes were obtained. By comparing the statistical results from different altitudes, it is determined that the dc ground-level TEF and corona inception field strength are linearly dependent on the altitude. Finally, the ground-level TEF and corona inception field strength altitude correction formulas of HVdc transmission lines are proposed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.