The abnormal heating test model of GIS internal insulation was established. The abnormal heating test of aluminum-filled basin insulator under steady state current was carried out. The content of SO2, H2S and CO2 remained stable at the beginning of the experiment, and the content of SO2, H2S and CO2 increased obviously when the experiment reached a critical point. The abnormal heating test model of the inner insulator of the gas insulated switchgear was established. The overheat test of solid insulation was carried out under the condition of 0.3 MPa absolute pressure in the gas chamber and without adsorbent. The overheat fault duration was 6 h and the overheat fault temperature was respectively 200℃、250℃, 300℃ and 350℃, the decomposition products of SF6 are CO, CO2, SO2, SOF2, H2S, COS and CF4. The generation mechanism of SF6 decomposition products under abnormal conditions is also analyzed to guide the judgment of internal faults and operation defects of equipment on site and ensure the safe and stable operation of power grid equipment.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.