Abstract

Our country has shown the significant features of high voltage direct current (HVDC) including multi-infeed and multi-send. Compared to multi-infeed system, there are a lot of weakness in the multi-send system, such as the grid structure is single and weak, which makes the interaction between AC and DC to a greater extent affect the stability of the multi-send hybrid AC/DC transmission system. In order to evaluating the system strength in multi-send hybrid AC/DC transmission system, for the first time, this paper proposed the general formula and simplified formula for multi-send short-circuit ratio (MSSCR), which accounts for the coupling between multi-dc projects. Considering the control characteristics of rectifier in sending-side and combining the maximum power curve method, the criticality of MSSCR is proposed. Multi-send critical short-circuit ratio (MSCSCR) is deduced by the quasi steady-state equation of rectifier, to determine the multi-send system is strength enough or not. The proposal of MSSCR is of considerable significance for effectively evaluating the stability performance of the multi-send AC/DC hybrid transmission system, completing the short-circuit ratio theoretical system, and consolidating the short-circuit ratio index status.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.