Abstract

In this paper, by studying the change rule of zero sequence voltage when single-phase leakage occurs, the detection method of insulation decline of mine cables is studied, especially the additional low-frequency signal sampling technology of power cables. Combined with the conventional leakage protection technology, the online monitoring equipment and supporting software for the insulation parameters of power cables are developed to realize the online monitoring of the insulation of each branch cable of the mine low-voltage power supply system and achieve the purpose of selective leakage protection.