Abstract

Two questions about zero-sequence-reactance relay to overcome the disadvantages of high fault resistance for single phase to earth fault of high voltage transmission lines are discussed in this paper. The first question is about the phase difference between the measured zero-sequence current and voltage at fault position for un-balanced transmission lines. The second question is about the “in-phase” problem in reactance relays (or fault component reactance relays). This paper analyzes the two questions theoretically and the reactance relay is improved by a new discriminative principle. The capability against the fault resistance is largely enhanced by the improved schemes. DOI: http://dx.doi.org/10.11591/telkomnika.v11i7.2835

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.