Electrically heated boiler is a large inertia, time invariant and nonlinear process. Classical PID control algorithm cannot make the system meet up the needs of performance index. Dynamic matrix control (DMC) predictive control algorithm is adopted to control electrically heated boiler temperature. Simulation result shows that the temperature control system’s overshoot is zero, settling time is 200s, the steady-state error is 9.7574e-006. Compared with PID control, DMC predictive control decreases the overshoot and settling time and improves the system dynamic performance. Aim at disturbance, improved DMC control algorithm is put forward and enhance the system disturbance suppression ability.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.