Abstract

It is currently estimated that with the increasing numbers of IT equipment, the amount of information data used by society will reach 200 times the present volume by 2025. Under such circumstances, there is an urgent requirement for cooling systems in server rooms with high density servers and compatibility with faster and larger servers along with high environmental efficiency. This survey carried out an experiment in which energy performance measurements with variance of outside air taken into the server room in a real size server room were taken. The results show that the cooling load of air conditioners could be approximately 90 percent less than that of the conventional air conditioning system for server rooms and that the overall energy consumption and COP are increased by 18 percent and 24 percent of the maximum respectively, compared to those of the conventional systems under maximum heat load conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.