Abstract

An electric boiler assisted air source heat pump heating system is used in a residential heat exchange station in Shijiazhuang for heating. However, in the actual operation process, there is a problem that the heating demand cannot be met. This paper studies the heating system. The results show that the problems are mainly manifested in two aspects: on the one hand, the operation strategy of heat exchange station is unreasonable; On the other hand, because of the close arrangement of heat pump units, the array cold island effect is produced, which affects the heating operation. Put forward a reasonable operation scheme for two aspects, and provide a reference case for central heating operation of air source heat pump in northern China.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.