Abstract

In order to obtain the time to failure of adjacent tanks under multi-thermal radiation conditions, the thermal response of gasoline tanks under multi-thermal radiation was studied. The heat radiation values of the adjacent tanks under pool fire were calculated. The temperature distribution and the corresponding stress of the adjacent tank were studied with ANSYS-Workbench software under the influence of single heat radiation and multi-thermal radiation. According to the physics properties of tank steel Q235B, the time to failure (ttf) of the tank was analysed. The results show that the temperature rise rate affected by the coupling effect of multi-thermal radiation is significantly higher than that affected by single heat radiation; when the storage tank is affected by the single heat radiation, the time to failure is about 22min; when the storage tank is affected by the coupling effect of multi-thermal radiation, the time to failure is about 15min.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.