Abstract

In order to apply dry ice to the insulator cleaning in power systems, it is necessary to obtain the optimal parameter range of each of the influencing factors. In this paper, a six-factor, five-level orthogonal test method is used to obtain a representative test plan. The influence level of air pressure, dry ice flow rate, cleaning distance, cleaning time, nozzle rotation speed and cleaning time on the cleaning effect were obtained. Results revealed that the optimal range for each cleaning parameter is: air pressure 0.7MPa∼0.8MPa, dry ice flow rate 2.5kg/min∼3.0kg/min, cleaning distance 10cm∼15cm, cleaning angle 10°∼20°, nozzle rotation speed 5∼15r/min, cleaning time 30s∼36s.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.