Abstract

As distribution flexible AC transmission system (DFACTS) technology is an economic and effective means to improve the power quality, the applied DFACTS devices are increasing. Therefore, the interactions among the DFACTS controllers should be considered. The paper establishes the linearized model of a single-load infinite-bus distribution system installed with a distribution static var compensator (DSVC) and a distribution static synchronous compensator (DSTATCOM), and the system transfer function can be obtained based on this model. Then, uses the relative gain matrix (RGA) method to analyze the interactions under different electrical parameters, drawing a conclusion that the interactions w ill be weakened when the electrical distances are increased and vice versa. The simulation results verify the effectiveness of the proposed model and the RGA method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.