Abstract

The purpose of this paper is to investigate the characteristics of direcct-contact condensation heat transfer. The jet of Freon vapor (R11 and R113) was injected against a uniform water stream in the vertical tube of inside diameter D=30mm. The temperature distribution in the vertical direction was measured for water flow rate Qw=5∼20×-6m3/s, Freon liquid flow rate Qf=0∼2.17×10-6m3/s and temperature difference ΔT=Ts-Tw=5∼35K. The results of experiment on the heat-transfer characteristics clarified the relation between the height of effective heat-exchange region, H and the ratio of heat-exchange quantity to its critical value, φ/φc.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.