Abstract
Lined ducts are widely used to reduce the noise generated from various equipments such as a large wind tunnel and exhaust pipes of engines. Especially the noise reduction is required in offices and hospitals accompanying with the spread of air conditioning equipments. The noise reduction of non-lined ducts is usually predicted by using the FEM and the BEM techniques. But, there were a few cases that the analytic value was compared with the actual measurement about the lined duct which the noise absorbing material was used for. In this research, the analytic value of BEM was compared with the actual measurement value for the attenuation quantity within a lined duct. Then, a noticeable gap was caused between the both results in specific frequency. So, the cause was probed with a viewpoint of the specific acoustic impedance ratio used for BEM. As a result, it was found that the prediction of sound attenuation of the duct agrees with the experimental result by applying the impedance measured by the impedance tube with φ100 diameter to the BEM analysis.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series C
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.