Abstract
Artificial pollution tests have been carried out to study AC flashover performances of various types of porcelain, glass, and polymeric insulators in this paper. The experimental results show that the polluted flashover voltage Uf is affected by equivalent salt deposit density rhoESDD and nonsoluble deposit density rhoNSDD, the influences of which are independent of each other. Based on the analyses of the flashover voltages, the correction formulas of the flashover voltages Uf of various insulators at various rhoESDD and rhoNSDD levels are pointed out. The experimental results also show that there is a distinct difference among the flashover voltages of various types of polluted insulators. At the same pollution degree, the antipollution performance of the fog-type glass insulator is better than those of the outer-rib porcelain insulators. In terms of the effectiveness of creepage distance of insulators, the antipollution performance of polymeric insulators is superior to those of porcelain and glass insulators.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.