Abstract

The hybrid ground heat exchangers (GHEs) of ground-coupled heat pump (GCHP) systems refer to a GCHP system using both vertical and horizontal GHEs. With the proposed optimal load ratio of horizontal to vertical GHEs, three-dimensional numerical heat transfer GHE models were established using independent heat transfer calculation method, and a design method for hybrid GHEs of GCHP system was put forward and then applied in one project. A combined heat transfer calculation method considering the mixing outlet water temperature was proposed and validated by a built experimental platform, which shows an improvement in accuracy prediction compared to the independent heat transfer calculation. It indicates the mixing outlet water temperature plays an important role in calculation accuracy and should serve as the boundary condition in modelling. The heat transfer performance of GHEs can be characterized by the independent heat transfer results in a certain range of load ratio.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.