Abstract
The faults Overhead line is generally caused by short circuit, overload, lightning surge, and tree. Distance relay is one of the protection equipments over the overhead line, and as the main protection by measuring fault impedance magnitude and comparing it to intended impedance. Distance relay setting has wide working area ranging from zone-1, zone-2, and zone-3. The setting must be adjusted when the equipment replacement exists. The replacement of overhead line conductor wire of ACSR 1 x 240 mm² into HVCRC 1 x 310 mm² and ACCC 1 x 310 mm² causing the necessity of re-setting adjustment in purpose of obtaining the appropriate one. This thesis is done by quantitative method which needs parameters in term of number. According to the calculation, the setting is obtained that zone-1 = 41,29257 Ω by t1 = instantaneous, zone-2 = 58,82457 Ω by t2 = 0,8 second, and zone-3 = 69,34377 Ω by t3 = 1,6 second.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: SAINSTECH: JURNAL PENELITIAN DAN PENGKAJIAN SAINS DAN TEKNOLOGI
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.