Abstract

Today, renewable energy projects connected to the interconnected network, with powers of the order of tens of megawatts, are more and more numerous in sub-Saharan Africa. And financing these investments requires a reliable amortization schedule. In the context of photovoltaic systems connected to the interconnected electricity grid, the quintessence of damping is the amount of energy injected into the grid. Thus it is fundamental to know the parameters of this network and their variation. This paper presents an evaluation of the impact of power grid disturbances on the performance of a solar PV plant under real conditions. The CICAD photovoltaic solar plant, connected to the Senelec distribution network, with an installed capacity of 2 MWp is the study setting. An energy audit of the plant is carried out. Then the percentage of each loss is determined: voltage drops, module degradation, inverter efficiency. The duration of each disconnection is measured and recorded daily. The corresponding quantity of lost energy is thus calculated from meteorological data (irradiation, temperature, wind speed, illumination) recorded by the measurement unit in one-minute steps. The observation period is three months. The total duration of disconnections related to the instability of the electrical network during the study period is 46.7 hours. The amount of energy lost is estimated at 22.6 MWh. This represents 2.4% of the actual calculated production.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call