Abstract
Purpose – The evolution of a semi‐open cooling circuit of a nuclear reactor was monitored over a two year period. The work aims to provide orientation elements for preventive procedures against localised corrosion.Design/methodology/approach – The water of the circuit was analysed in stagnation and in circulation, at various sampling points. The rust was analysed by neutron diffraction and the surface quality of the steel was checked by microscopic observations.Findings – The obtained results did not confirm the presence of rust in iron compounds supported by chlorine, such as the Akaganeite, β‐FeOOH. In addition, chemical analysis of water showed that, after two years, the increase of chlorine concentration and water conductivity remained weak. Moreover, the pH was maintained within values favourable rather to the passivation of the steel.Practical implications – It was deduced through this work that the dosing of the circuit with chlorine was not sufficient that it should require an annual replacement o...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.