Abstract

AC traction systems are 1 $\times$ 25 or 2 $\times$ 25 kV/50 Hz single-phase, nonlinear, time-varying loads that can cause power-quality problems, such as unbalanced or distorted voltages. To reduce unbalance, external balancing equipment is usually connected to these systems, forming the Steinmetz circuit. Parallel resonances can occur in these types of circuits, exciting the harmonic emissions (below 2 kHz) of railway-adjustable speed drives. This paper studies these resonances at pantograph terminals and provides analytical expressions to determine their harmonic frequencies. The expressions are validated from several traction systems in the literature and PSCAD simulations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.