Abstract
Concepts of maximum power transfer of DC systems and associated AC voltage variations, particularly at inverter stations having low short-circuit ratios, have been extended to include various AC load models and an AC line in parallel with the DC line. The operating capabilities are shown to vary from those predicted from either a Thevenin AC source model or the corresponding short-circuit ratio. The study used an AC/DC load flow program.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.