Abstract

This paper investigates microgrid transient stability with mixed generation—synchronous generator (SG), grid-forming (GFM) and grid-following (GFL) inverters—under increasing penetration levels toward a 100% renewable generation microgrid. Specifically, the dynamics of a microgrid with an SG and GFL inverter(s), an SG with GFM inverter(s), and an SG with GFM and GFL inverters under each penetration are evaluated with an electromagnetic transient study with two critical dynamic events: unplanned islanding and switching in a pumped induction motor load. Analysis and simulation results indicate that the microgrid with GFL inverters running in parallel with the SG can provide a faster power response than the GFM inverters to compensate for the deviations of the frequency and voltage. The scenario with the mixed SG, GFM, and GFL inverter has the best transient and steady-state stability toward 100% inverter-based resource (IBR) penetration. This comprehensive study provides helpful references for microgrid engineers to understand the microgrid stability when facing various choice of installing IBRs (GFL, GFM, or mixed).

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call