Abstract

Closed chamber fires are studied by burning four types of organic liquids, namely ethanol, N-heptane, thinner and kerosene. The burning be haviour of the liquids was observed, and the hot gas temperature measured. Transient variations of the temperature are also compared with those pre dicted by three fire zone models which can be used to simulate a closed cham ber fire. The three selected fire zone models are the ASET, the CFAST and the CCFM.VENTS. All were developed at the Building and Fire Research Labora tory, NIST, USA. The ASET model was run by the menu-driven program FIRE- CALC developed at the Division of Building and Construction, CISRO, Aus tralia. The models ASET and CCFM.VENTS are found to be very suitable for predicting the hot gas temperature in a closed chamber as used in this study. Lastly, the response of four types of detectors are studied.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.