Abstract
This paper reports on an investigation of the effects of fire on long span truss floor systems in a tall building environment. The effects of fire spread over multiple floors of a building are the focus of this research, especially where this may lead to progressive collapse. The results from an investigation of a two-dimensional model of a multistory office building analysis are presented. The model is representative of the type of construction used in the World Trade Center Towers 1 and 2. The local and global response of the model is described over the course of a concurrent fire on three floors reaching a peak compartment temperature of 800°C. The results of the analysis show that large displacements may occur in long span structural floor systems without failure, however, the interaction of the highly deflected floors with the exterior or perimeter columns can lead to structural collapse. Additional structural members, such as hat trusses, that allow redistribution of loads away from the exterior columns to the core columns have a significant beneficial impact on the robustness of the structure.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.