Abstract

An ice storm in Central Iowa on March 7, 1990, caused the domino failure of 69 H frame steel pole structures that were part of a 345 kV transmission line covering a distance of approximately 30.6 km (19 miles). This paper briefly documents the damage, and presents the nonlinear structural analyses performed on a portion of the above transmission line using the ETADS software, which is a structural finite element submodule of TL Workstation software. The analysis included a characterization of the likely storm loads and their application to the transmission systems. The methodology used in trying to simulate the sequence of events leading to the failure is also presented. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.