Abstract

This paper presents an investigation on the structural analysis of a steel column exposed to a localized fire. Because EN 1991-1-2 does not provide a simplified method to calculate heat transfer to vertical elements, a CFD (Computational Fluid Dynamics) model of a localized fire is developed, based on previously conducted experiments. Furthermore, a heat transfer analysis was performed based on the results of CFD modeling and for the ISO temperature–time curve. Finally, a nonlinear structural analysis of the steel column was conducted for the localized fire scenario, as well as for the ISO temperature–time curve. A comparison between the localized fire and ISO fire exposure points indicates that localized fires can cause earlier failure of a column, depending on the level of external load.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.