Abstract

Interests on ester liquids as replacement of mineral oil in large power transformers are growing in recent years. This paper presents experimental studies on streamer and breakdown in synthetic and natural esters. Lightning impulse voltage was chosen when considering the practicality of standard tests of transformer industry. First, streamer length, velocity, shape and mode were analyzed based on optical images obtained by a multi-channel ultra high speed camera. Under the same voltage level, streamer in both natural and synthetic esters propagates faster and further, with more branches, than in mineral oil. Breakdown tests at various gaps from 15 mm to 100 mm were conducted, and it was found that fast streamer led breakdown becomes statistically dominant in a large gap under lightning impulse and ester liquids have lower breakdown voltage than mineral oil due to their low tolerance to fast streamer. Therefore a relationship between the results under lightning impulse and previously published results under step voltage was built up and an empirical formula was obtained to predict the breakdown voltage of esters at very large gaps.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.