Abstract
Base on three dimension (3D) finite element method (FEM), a electromagnetic model for a power distribution transformer is established. The core loss, stray losses in structural components are simulated, the effects of magnetic shunts on tank losses are studied, then compared with experiments. The core loss, the decrease of stray losses when using magnetic shunts are in accordance with experiments. Studies indicate that tank loss is the most impartment part of stray losses in this model, magnetic shunts are effective in reducing stray losses.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.