Abstract

Numerical study results are present to demonstrate strategies to increase the robustness of endplate beam–column connections at elevated temperatures in a fire. Proposed strategies include increasing the bolt grade or diameter, adopting dog-bone shaped beam, channel endplate or spaced endplate connections. Numerical results show that adopting different endplate connection types (extended end plate, flush endplate, and flexible endplate) or increasing the bolt load baring capacity (increase its grade or diameter) only have very limited effects to increase the robustness of the connection during catenary stages of the framed beam in a fire. Appropriate treatment of the endplate or the steel beam can achieve satisfactory consequences. The adoption of either dog-bone shaped beam, bolted channel extended endplate or spaced extended endplate connection can increase the robustness of connection, which allows the connection to survive over 100°C higher in critical temperature.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.