Abstract
This paper presents the analysis of voltage flicker for an industrial power system by considering the stochastic load modeling of arc furnaces. The field measurement of power consumption has been performed to identify the variances of injection current at each load bus. The mean value and standard deviation of the voltage flicker are then solved by stochastic load flow analysis with the fluctuation of reactive power consumption by arc furnaces. To investigate the mitigation of voltage flicker by static var compensator, the mathematical models of SVC has been included in the computer simulation to find the adaptive reactive power compensation. It is found that the variation of voltage flicker at each bus can be determined accurately by the proposed stochastic load flow analysis and the quick response of SVC to the bus voltage change can effectively reduce the voltage flicker.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.