Abstract

Evaluation of harmonic distortion and power quality in electrical networks cannot neglect the stochastic approach, which takes into account the random nature of harmonics injected in the network by distorting loads. In this paper, procedures are proposed to evaluate the resultant probability density and cumulative functions of the sum of harmonic currents at buses of electrical networks. These procedures are applied to the results of long-term measurements performed on MV networks, which supply both residential and industrial loads. It is shown that the time series associated to real and imaginary components of harmonic currents are, in general, nonstationary, so that the statistical tools proposed in literature to evaluate the probability function of the magnitude of the sum of random vectors may give inaccurate results. On the contrary, the proposed procedures allow accurate estimates of the sum of harmonics, associated to given probabilities, to be achieved.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.