Abstract

Abstract The proposed heavy water moderated and light water cooled pressure tube type boiling water reactor works on natural circulation at all power levels. It has parallel inter-connected loops with 452 boiling channels in the main heat transport system configuration. These multiple (four) interconnected loops influence the steam drum level control adversely through the common reactor inlet header. Alternate design studies made earlier for efficient control of SD levels have shown favorable results. This has lead to explore further the present scheme with the compartmentalization of CRIH into four compartments catering to four loops separately. The conventional 3-element level control has been found to be working satisfactorily. The interconnections between ECCS header and inlet header compartments have also increased the safety margin for various LOCA and design basis events. The paper deals with the SD level control aspects for this novel MHT configuration which has been analyzed for various PIEs (Postulated Initiating Events) and found to be satisfactory.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.