Abstract

In the present investigation, the steady state performance of a rectangular single phase natural circulation loop (NCL) with end heat exchangers is studied. One-dimensional governing equations are considered in developing the mathematical model. Analytical expressions are derived for the circulation rate and temperature profile. However, the individual performance parameters are to be computed iteratively as the equations are strongly coupled. A suitable iterative procedure is given to evaluate the important loop parameters such as steady state flow rate, and riser and downcomer temperatures. Few special cases are discussed where analytical expressions for circulation rate and temperature distribution can be obtained directly without any iterative procedure. It is also shown that both the hot and cold end heat exchangers should have equal conductance (UA) for maximization of circulation rate. This feature of NCL is identical with heat power cycle and can be explained in light of equipartition principle.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.