Abstract

AbstractBecause of the lower insulation level than for transmission lines, in this study on lightning protection design of distribution lines, not only direct lightning strokes but also induced voltages caused by nearby strokes must be taken into account. Thus, it is necessary to grasp the frequency of occurrence of lightning phenomena around distribution lines. For this aim, lightning phenomena on TEPCO's distribution lines in use were continuously observed for 6 years (1996 to 2001). Through this observation, new interesting statistical data that can be a useful basis for rationalization of lightning protection design of distribution lines were obtained. Two hundred and four lightning strokes were observed through the six‐year period. Probability of occurrence of a direct stroke was 22% (45 direct strokes were obtained). The fact that in 47% of direct strokes the electric outage did not occur is very interesting. Moreover, the value of surge discharge current of the arrester in the case of nearby stroke is the basis for conventional theory of grounding system. Therefore, statistical analysis of ZnO discharging current in the case of nearby strokes was carried out. As a result, in the case of nearby strokes, 5% value of cumulative frequency of discharging current is 0.5 kA. This value is half the conventional data. © 2006 Wiley Periodicals, Inc. Electr Eng Jpn, 155(2): 8–16, 2006; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20180