Abstract

AbstractThe impact of 48‐pulse STATCOM/SVC on the apparent impedance seen by the transmission line distance relay is investigated in this paper. Analytical results are presented and verified by detailed simulations. The STATCOM/SVC control systems are modeled in full details and practical constraints are applied. It is shown that the presence of a current limiter in the control system of STATCOM could significantly mitigate the impact of STATCOM on the relay's calculated apparent impedance. Six different phase‐to‐phase and phase‐to‐ground measuring units of the distance relay are simulated to resemble the behavior of the relay. It is shown that the impact of SVC on the apparent impedance seen by the phase‐to‐ground fault measuring units is more pronounced. Different power system operating conditions, STATCOM/SVC control system settings and fault scenarios are considered in the simulations. The STATCOM/SVC effects on the distance relay tripping characteristics are also analyzed. © 2011 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.