Abstract

This paper presents static synchronous compensator (STATCOM) integration into a doubly-fed induction generator (DFIG) based wind park (WP), analyses the impact of STATCOM on the WP high voltage ride-through (HVRT) capability, and proposes a transient function for the STATCOM to improve the WP HVRT capability. An actual WP is adopted as a test system. The STATCOM size is selected considering the grid code requirement for power factor control, and various wind turbine (WT) and medium voltage (MV) feeder outage scenarios. The WP HVRT capability is assessed with electromagnetic transient (EMT) simulations by analyzing the responses to a parametric voltage waveform. The external system is represented by a Thevenin equivalent. The pre-described voltage waveforms are applied to the Thevenin source in order to assess the conformity of the HVRT capability to Hydro-Quebec specifications. The WP simulation model includes all details regarding collector grid and overvoltage protection. The simulation results demonstrate that, STATCOM usage provides a noticeable improvement in HVRT capability of the WP, especially with the proposed transient function.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.